Products:Cummins Diesel Generator Set

Cummins Diesel Generator Set
Electricity has become more and more important with the development of industry. Diesel Generator Sets are used to generate electricity to meet the electricity requirement of establishments such as Hotels, Railway Stations, Telephone Exchange, Schools, and Shops etc. Our Company's Diesel Generator Sets, especially three phase generators have got high reputation in the market for their maximum performance, reliability and longevity. Now, Dingxin has an average supply of over 4,000 diesel generator sets a year.
Cummins Diesel Generator Set:STANDARD SPECIFICATIONS DCS 200
Ambient conditions: 1,000 m bar, 27, 30% relative humidity. Rating is according to ISO 3046 and 8528.
Available in the following voltages: 440/254-415/240V-400/230V-380/220V-220/127V-200-115V.
ESP: Standby Power Standby duty, operation under variable load, without over load.
Generator set, 50HZ at 1500 RPM, Three Phase, 400/230V CUMMINS Engine, 1500RPM
Model Tank
(L)
Noise
Level
dB(A)
KVA KW Model Bore/
stroke
mm
Cyl. Asp. Gov.
ESP PRP ESP PRP
DCS200 400 98 275 250 220 200 NTA-855GA 140/152 6L TC E

PRP: Prime Power-Continuous duty operation, under variable load 24/24h-10% over load permissible 1 hour/12 hours.
(1) M: Mechanical speed governor, E: Electronic speed governor.
(2) NA: Naturally aspirated, TC: Turbocharged, TCA: Turbocharged and air-air after cooled. TW: Water-cooled Turbocharged.

Cummins Diesel Generator Set features:
Composed of Cummins diesel engine and Stamford alternator
Engine Charge alternator 24 V
Single bearing alternator IP 23, insulation class H
40℃radiator as standard, 45℃is optional, water-cooled
Skid and vibration isolators
Dry type air filter, Main line circuit breaker
Microprocessor control panel, Key start panel be optional
4 pole MCB, 24 V battery, rack and cable
8-hour operation base tank
Special Integrated Steel Base tank and sprayed overall in gloss enamel pain
Optional soundproof or weatherproof canopy, Industrial or residential silencer be optional

Cummins Diesel Generator Set:Voltage Regulation
Voltage regulation maintained within ±0.5% as follow:
Between 0.8 and 1.0 lagging and unity
From no load to full load
At speed droop variation up to 4.5%

Cummins Diesel Generator Set:Frequency Adjustable Ratio
Change load from 0-100%, within 1.0% (electric speed regulator), within 4.5% (mechanical speed regulator)
Frequency Undulation:
Load from 0-100%, Frequency undulation within 0.25%
No load wire volts max undulation ratio within 1.8%
Three phrase balanced load in the order of 5%

Cummins Diesel Generator Set:Effect factor of telecom
TIF better than 50
THF to BS4999 Part 40 better than 2%

Cummins Diesel Generator Set:Electromagnetism
In compliance with BS800 and VDE levels G and N
ISO3046, ISO8528, BS4999, BS5514, BS5000PT99AS1359, IEC34, UTE5100, VDE0530, ISO9001:2000, ISO14001 & CE certified

 

Cummins Diesel Generator Set:Engine Specification
Cummins Diesel Engine
Designed with Safety in Mind
Cummins water cooled diesel engine, oil and fuel filter fitted, Water separator, Lube-oil drain valve fitted.
Cast lron Skirted Block:
With main bearing supports between each cylinder, for maximum strength and rigidity, low weight, and optimum crankshaft support.
Compact Size:
For ease of installation and easy access for routine maintenance.
Direct Fuel Injection System:
With high swirl intake ports for thorough mixing of air and fuel to provide low fuel consumption.
Forged Steel, I-Beam Cross Section Connecting Rods:
With angle split cap-to-rod interface and cap screw attachment.
For maximum structural strength and ease of service.
Filters:
Air cleaner with dry element and restriction indicator. Spin full flow lube oil filter.
Cooling:
40℃ radiator as standard, Oil cooler, Drain tap.

Cummins Diesel Generator Set:Technical Data

Engine Model   NT855GA
Engine Manufacturer /Brand   Cummins(China)
Type and Cylinder   6L, 4-Zyklus
Induction system   TC
Bore×Stroke mm 140×152
Compress the ratio   15:1
Engine Speed   1500
Continuous Rated Output kw 310
Oil Capacity L /
Coolant Capacity L NA
Starting System   Electric-24 volt DC
Displacement L 14
Capacity L 38.6
Battery Voltage /Capacity   24VDC/630A/600
Exhaust Gas Flow l/s 894
Exhaust Temperature 410
Fuel Consumption 100% L/hr 55
Fuel Consumption 75% L/hr  
Fuel Consumption 50% L/hr  
Governing Type   E


AC Alternator
STAMFORD NEWAGE GENERATOR END
STAMFORD NEWAGE has a long history of producing high-quality reliable products for the power generation market. Their portfolio of high quality generator ends is recognized as an industry standard.

Alternator Technical Data
Stamford AC alternator

Brushless, self exciting
Class ‘H’insulation
Standard degree of protection is IP23
Self regulating
With fan cooling
Resist humid grease
AC excitation, rotating rectification tube
Stator grease insulation covered
Rotator and excitation high polymer
Resist the corruption of oil and acid.
Rotator balance is in accordance with BS5625 standard 12.5
High-quality lubrication sealed long-time bearing
Rotator silicon steel close tight

Cummins Diesel Generator Set: Alternator Technical Data
Generator Model UCD1274K
Exciter Brushless
Cooling Fan Cast alloy aluminum
Bearing Single, double shielded
Windings 100%copper
Connection Type Reconnectable
Insulation Type Class H
Pitch 2/3
Amortisseur Winding Full
A.V.R.Model S×460
Voltage Regulation NL-FL ±0.5﹪
Underspeed Protection Standard
Overexcitation Protection IP23
Standards NEMA,1EC,1EEE,CSA,BS
Phase Sequence A(U),B(V),C(W)
TIF(1960 Weightings) <50
Excitation Self-exciting PMG optional

Cummins Diesel Generator Set: Control System
The DSE501 is a Manual Start Control Module, which has been designed to manually control the engine via a key switch on the front panel. The module is used to start and stop the engine, indicate fault conditions, automatically shut down the engine and show the fault condition by LED.
The module has the ability to monitor the following conditions: Low Oil Pressure, High Engine Temperature, Auxiliary Shutdown and Overspeed. Each alarm channel has its own LED indicator and once activated no further alarm conditions will be accepted
Cummins Diesel Generator Set: Main Features
1.Oil Pressure Monitoring
2.Engine Temperature Monitoring
3.Overspeed Protection
4.Charge Failure Warning

The module is operated via a three position key switch mounted on the front panel with Stop, Run and Start positions. In the Stop position the DC supply is removed from the module and the run relay and alarm output are de-energised.

Cummins Diesel Generator Set: Operation:
If the switch is turned to the Run position the module is powered up and the run relay is energised, activating the engine fuel/ignition system and the protection hold off timer is initiated. If the switch is moved to the Start position and held against the spring position, a positive supply is applied to the relevant output terminal and on to the starter motor. Once the engine has started, the switch should be released and allowed to return to the Run position.
CCB PARALLELING SYSTEM TRAILER SET ATS